C2E616302_MB_C1 Schneider Cuadro H Sixfold Metal Plate KNX Switch Interface Matte Black 13mA ETS Programmable
The C2E616302_MB_C1 is the six-gang metal keypad from the Cuadro H range in matt black. It combines the largest practical gang count below the eight-gang plate with the heaviest faceplate in the family. The article number follows a consistent rule: 302 denotes six gangs, 02 declares a metal faceplate, MB indicates matt black, and only the colour code at the end and the C1 suffix for the sales area vary.
Technically, it is the same bus participant as every other Cuadro H keypad: 21 to 30 V DC from the KNX line, approximately 13 mA at 24 V, a coupling unit integrated in the housing, a two-core bus connector with red to plus and black to minus, and no mains connection. Because there is no mains connection, the plate carries no load rating and can be re-tasked to lighting, blinds, or scenes without rewiring. The envelope measures 86 × 86 × 29 mm, and the declaration is CE with KNX certification, IP20, for indoor use.
| Order Number | C2E616302_MB_C1 |
|---|---|
| Number of Gangs | 6 |
| Faceplate Material | Metal (code 02) |
| Finish | Matt black (磨砂黑) |
| Product Range | Cuadro H, marketed as Jingyue series in China |
| Product Type | KNX push button, programmable per button |
| Bus and Network Type | KNX TP, bus powered |
| Power Supply | KNX port, DC 21 to 30 V, approx. 24 V at 13 mA |
| Rated Current (Reference Designation) | 15 mA at 21 to 30 V DC |
| Bus Connection | KNX connecting connector, red core to plus, black core to minus |
| Bus Coupling | Integrated coupling unit inside the device |
| Proximity Sensing | Microwave technology, default and high sensitivity levels, panel material selected in ETS |
| Button Handling | Buttons are not removable; icons are changeable |
| Mounting | Flush mounting in a wall box of 35 mm depth or more (wall box not supplied) |
| Retaining Ring Torque | Maximum 6 kgf·cm |
| Dimensions | W 86 mm × H 86 mm × D 29 mm |
| Operating Temperature | −5 to +45 °C |
| Storage Temperature | −20 to +60 °C |
| Relative Humidity | 10 to 93 %, no condensation |
| Installation Altitude | 2000 m or below |
| IP Protection Rating | IP 20, indoor use only |
| Certifications | CE, KNX certified |
| Scope of Supply | Device, metal retaining ring, two M4.0 × 25 mm screws, KNX bus connector, instruction sheet, dust prevention cover |
| Commissioning | ETS download, red programming LED, green LED slow flash after download, approx. 10 s initialisation |
| Life Cycle Carbon Footprint | 10 kg CO₂ equivalent per unit as published by Schneider Electric |
| Recyclability Potential | 28 % as published by Schneider Electric |
| Packaging | Recycled cardboard, at least 70 % recycled content |
Two commissioning points carry more weight on this variant than on the plastic plates.
- Sensing parameter: Proximity detection is by microwave. The instructions state that sensitivity depends on the panel material, and both the material and one of two sensitivity levels are set in ETS. A metal plate must be declared as metal, or the plate will sense unpredictably.
- Metal front and the SELV rule: The device must be installed to SELV wiring regulations. Where it shares a multi-gang frame with 230 V accessories, the installer is responsible for maintaining the separation, insulating the shield, the stability wire, and the white and yellow cores, and landing only the red and black bus cores.
This plate is specified where six gangs of control and a metal finish are both non-negotiable, which usually means a premium interior with a layered lighting design.
- Hotel suites and club rooms: Used where the entrance position controls several lighting groups, the curtain, and a stored scene, and the wall is a dark veneer that a polymer plate would fail to match.
- Executive floors and boardrooms: Applied where the hardware is specified to the same standard as the joinery.
- High-end residential projects: Used in principal living rooms where the lighting is designed in layers and the client has asked for metal throughout.
- Restaurants and private dining rooms: Taken where the scene changes between service periods and the fittings are black, and where a project already uses metal two- and four-gang plates elsewhere — this version keeps the larger rooms consistent in material while the gang count rises with the complexity of the lighting.
KNX switch interface matte black
,sixfold metal plate push button panel
,ETS programmable 13mA KNX interface
-
NP16164_01BK_E1 Schneider Unica Range KNX Wall Station with Eight Keys Black Status LEDs Bus Coupler
Product Overview The NP16164_01BK_E1 is the eight-key version of the Unica KNX wall station, supplied in black. With eight keys on an 86 millimetre plate, it is the largest configuration in this family and behaves more like a dedicated controller than a switch plate. The design principle behind the ... -
NP16162_01MS Schneider Unica KNX 4 Key Push Button Metallic Silver Backlit Scene Control Panel Unit
Product Overview The NP16162_01MS is a four-key Unica KNX push button in a metallic silver finish. This variant of the four-key panel is chosen where the device is visible against a metal or light surface, and the design intent is that the control should read as part of the architecture. Four keys ... -
N 528C01 5WG1528-1CB01 KNX Universal Dimmer 2 Gang 150VA 120V UL LED Compatible 4MW
N 528C01 5WG1528-1CB01 KNX Universal Dimmer 2 Gang 150VA 120V UL LED Compatible 4MW N 528C01 is the 120 V variant of the two-channel universal dimmer, released for the North American market and listed by a recognised testing laboratory. It follows the same universal philosophy as its 230 V sibling: ...