R9MUX6M Schneider Resi9 PowerTag Universal Energy Meter Three Phase 250A Six Channel Modbus RTU Rail
The R9MUX6M is the universal energy meter of the Schneider Resi9 PowerTag family. "Universal" here means a single catalogue number covers both three-phase and single-phase circuits, depending on which current transformers are used. With the 80 A transformer the basic current is 5 A and saturation falls at 80 A; with the 160 A or 250 A transformer the basic current becomes 10 A and saturation moves to 160 A or 250 A respectively. This allows the same meter to serve a domestic final circuit and a small commercial feeder without a second catalogue number.
It is a 3P+N device measuring 36 mm wide, 114.6 mm high and 70 mm deep. It takes its voltage reference from a 230 V phase-to-neutral supply with 20 % tolerance, and reports over RS485 using Modbus RTU at Class 1 for active energy and Class 0.5 for voltage and current to IEC 61557-12.
| Catalogue reference | R9MUX6M |
|---|---|
| Range | Resi9, PowerTag Energy family |
| Device type | Universal energy meter, three-phase or single-phase circuits |
| Poles | 3P and N |
| Maximum current | 250 A |
| Basic current | 5 A with the 80 A transformer; 10 A with the 160 A and 250 A transformers |
| Starting current | 20 mA with the 80 A transformer; 40 mA with the 160 A and 250 A transformers |
| Saturation current | 80 A, 160 A or 250 A according to the transformer fitted |
| Channels | Six measuring channels through MTP transformers |
| Conductors | Four-wire connection |
| Voltage circuit | 230 V AC, 50 Hz, ±20 %, phase to neutral |
| Own consumption | 3 W maximum |
| Communication | RS485, Modbus RTU |
| Accuracy, active energy | Class 1 to IEC 61557-12 |
| Accuracy, reactive energy | Class 2 to IEC 61557-12 |
| Accuracy, active power | Class 1 to IEC 61557-12 |
| Accuracy, apparent and reactive power | Class 2 to IEC 61557-12 |
| Accuracy, voltage and current | Class 0.5 to IEC 61557-12 |
| Quantities measured | Energy and power in all three forms, voltage, current |
| Standards | IEC 61010-1, IEC 62052-11, IEC 62053-21, IEC 61557-12 |
| Mounting | 35 mm DIN rail |
| Width | 36 mm |
| Height | 114.6 mm |
| Depth | 70 mm |
| Weight | 121 g |
| Colour | White RAL 9003 |
| Overvoltage category | III |
| Measurement category | III |
| Pollution degree | 2 |
| Ingress protection | IP 20, impact IK05 |
| Operating temperature | −25 to +60 °C |
| Storage temperature | −40 to +85 °C |
| Humidity | 5 to 95 % at −25 to +60 °C |
| Altitude | 0 to 2000 m |
| Carbon footprint | 55 kg CO₂ equivalent, 39 kg of it in the use phase |
| Recyclability potential | 11 % |
| Take back | Covered by a take-back scheme |
The reason to choose the universal version over the single-phase meter is rarely the channel count — which is six in both cases — but the ability to meter a three-phase feeder as one logical load while still allocating channels individually. On a heat pump or a small chiller, the three phases carry the compressor and the auxiliaries in a way that makes per-phase data useful for fault finding. The Modbus register map exposes voltage and current per phase as well as the aggregated power, so an unbalanced phase is visible rather than averaged away.
The same caution applies as with the single-phase unit: the transformers determine the accuracy, the conductor must pass through the core alone, and the device is rated for installation inside a distribution board at overvoltage category III and pollution degree 2 — not for a damp plant room wall. At 36 mm, the unit occupies one and a half standard devices, which is the detail that decides whether it fits the board that already exists.
Universal three-phase metering suits small commercial boards where the loads are mixed and the client wants one interface. Typical applications include:
- Heat pump and chiller installations — separate the compressor from the auxiliary circuits for clearer diagnostics.
- Small office boards — apply to lighting, socket, HVAC and kitchen circuits where three-phase distribution makes per-phase visibility worthwhile.
- Retail units with three-phase supplies — refrigeration and lighting sit on different phases, so a phase imbalance becomes an early warning of a failing cabinet.
- Workshops and light industrial units — apportion consumption between machines and general power.
- Multi-let buildings — where a single three-phase intake serves several tenants and the split has to be defensible.
Because the same meter accepts 80 A, 160 A or 250 A transformers, a board can be re-metered later without replacing the electronics — the practical argument for the universal variant over the fixed single-phase unit.
Schneider Resi9 PowerTag energy meter
,Three phase 250A Modbus RTU meter
,Six channel rail energy meter
-
C2E616102_ST_C1 Schneider Cuadro H 2-Gang Stainless Steel KNX Keypad 86mm Square SELV Bus Node ETS
Product Overview Stainless steel is the finish most often specified for the wrong reason. The C2E616102_ST_C1 is the two-gang Cuadro H keypad with a stainless face, and buyers usually arrive at it because they want the plate to match door ironware or a kitchen splashback — not because they have ... -
C2E616202_MB_C1 Schneider Cuadro H Fourfold Metal Plate KNX Switch Interface Matte Black 13mA ETS Ready Device
Product Overview The C2E616202_MB_C1 is the metal four-gang keypad of the Cuadro H range in matt black — the variant positioned between the plastic four-gang plate and the glass version in the same colour. The article coding is consistent across the family: the 202 block denotes four gangs, the ... -
C2E616201_GY_C1 Schneider Cuadro H Fourfold KNX Switch Interface Light Grey Polymer 13mA IP20 Indoor Plate
Product Overview The C2E616201_GY_C1 is the four-gang grey plastic keypad of the Schneider Cuadro H family — the configuration most commercial rooms settle on once lighting has been split into a general group, a perimeter or feature group, and a blind. The article number identifies it precisely: the ...